CANARYPredictive Valve Integrity

Connectors & valve compatibility

The connector decides what can be measured

Hydraulic valves do not share one electrical interface. Two valves can use the same physical connector and assign completely different signals to the same terminal. CANARY is built around that reality: connectors are specified per order from your valve’s data sheet, and what the monitor can detect follows directly from which signals that interface actually carries.

The principle

Same standard, different pinout

A Bosch Rexroth 4WRPEH and a Moog D633 both use a 6+PE circular connector. On the Rexroth, terminal C is the position-signal reference. On the Moog, terminal C is the enable line. The connector is interchangeable; the wiring is not.

What follows

Coverage tracks the interface

A valve whose connector carries no spool-position feedback cannot be monitored for hysteresis, response threshold or null behaviour — by any device. We state that per valve rather than implying uniform coverage.

How we handle it

Built to your data sheet

Send the valve data sheet with the order. The plant-side and valve-side connectors are built to that valve’s interface and pin assignment, and we confirm in writing what the monitor will and will not see on it.

Interface standards

Connector standards used on hydraulic valves

The interfaces CANARY is supplied against, and what each one makes available to a monitor.

Hydraulic valve electrical interface standards
StandardDescriptionCANARY coverageSignals carried
DIN EN 175201-804
6+PE and 11+PE
Circular, screw-locking. The dominant interface for proportional and servo valves carrying on-board electronics. Formerly DIN 43563.FullSupply, enable, command, actual value, fault output and PE, depending on variant.
DIN 43563
6P+PE
The earlier designation still quoted in much Bosch Rexroth literature. Mechanically interchangeable with the 6+PE above, but the signal on each terminal differs by manufacturer.FullSupply, command pair, position reference and a test or monitor output.
MIL-C-5015 style
7-pin and 12-pin
Circular bayonet or threaded. Used by Atos and others for proportional valves with integral drivers; the 12-pin variant follows DIN 43651.FullSupply, enable, flow reference, flow monitor and fault output.
DIN EN 175301-803 Form A
2+PE or 3+PE
The square solenoid connector, 18 mm pin spacing, formerly DIN 43650 Form A. Fitted to on/off and simple proportional solenoids with no on-board electronics.PartialCoil supply only. No command or position feedback exists on this interface.
DIN EN 175301-803 Forms B and C
2+PE or 3+PE
The smaller micro (10–11 mm) and sub-micro (8–9.4 mm) solenoid connectors.PartialCoil supply only.
M12 A-coded
4-pin and 5-pin
Used for IO-Link Class B valve control, auxiliary transducers and fieldbus drops rather than for the main analogue interface.PartialSupply and digital communication; analogue command and feedback are not present on an IO-Link drop.

Full means the interface carries a command and, in most cases, a position feedback signal, so the complete measurement set applies. Partial means the interface carries coil supply only — the monitor still measures supply voltage, current, vibration, acoustic emission and oil temperature, which covers coil degradation, cavitation, wiring and supply, but not the spool-behaviour modes.

Valve reference

Ten common proportional and servo valves

Compiled from the manufacturers’ own published documentation. Pin assignments vary by ordering code and revision even within a series, so treat this as a planning reference and confirm against the data sheet for your exact part number.

Valve interface reference — verify against your valve’s data sheet before ordering
ValveConnectorPin assignmentCommand signalCANARY coverage
Bosch Rexroth
4WRPEH 6
Proportional directional, direct operated
6P+PE, DIN 43563A 24 V · B 0 V · C LVDT reference · D setpoint + · E setpoint reference · F test signal · PE±10 V (A1) or 4–20 mA (F1)Full
Command, position reference and the test/monitor output are all present, so hysteresis, threshold, null behaviour and tracking are all measurable.
Bosch Rexroth
4WRPEH 10 / 4WRPEH 16
Proportional directional, larger frame sizes
6P+PE, DIN 43563Same family assignment as 4WRPEH 6±10 V or 4–20 mAFull
As above. Larger frames draw more current — confirm the valve stays within the 5 A monitor limit.
Moog
D633
Direct drive servo-proportional
6+PE, EN 175201-804A 24 V · B GND · C enable · D command · E command reference · F actual value · PECurrent or voltage input; 4–20 mA or 2–10 V outputFull
A dedicated enable line means enable-to-acknowledge timing and the electronics mode are both measurable. Zero-lapped spool, so internal leakage detection applies with transmitters fitted.
Moog
D634
Direct drive servo-proportional, larger frame
6+PE, EN 175201-804As D633Current or voltage inputFull
As D633.
Moog
D636 / D638
Direct drive with extended I/O
11+PE, EN 175201-8043 enable · 4 command · 5 command reference · 6 actual value · 8 valve-ready digital output · 9 24 V · 10 GND · 11 monitoring output · PECurrent or voltage inputFull
Two digital status outputs in addition to the analogue set, giving the richest signal picture of any interface listed here.
Parker
D1FP
Direct operated servo-proportional
6+PE (code 0/7) or 11+PE (code 5), EN 175201-804Command on terminals D and E (6+PE) or 4 and 5 (11+PE); enable present on code 70–±10 V, 0–±20 mA, 4–20 mA or 0–±50 mAFull
Command options span four of CANARY’s supported ranges including ±50 mA. Confirm terminal numbering against Parker’s operating instructions.
Parker
D3FP / D*1FP
Direct and pilot operated proportional
6+PE or 11+PE, EN 175201-804As D1FP by ordering code±10 V, ±20 mA, 4–20 mA or ±50 mAFull
Same interface family. The IO-Link Class B variant uses M12 instead and carries no analogue command.
Atos
DHZO-TES / DKZOR-TES
Digital servo-proportional directional
7-pin ZM-7P / ZH-7P, MIL-C-5015 styleA 24 V · B 0 V · C enable · D flow reference + · E reference − · F flow monitor · G fault output±10 V standard, 4–20 mA with /IFull
Carries a dedicated fault output, so the valve’s own health signal is monitored alongside the measured signature. A 12-pin DIN 43651 variant exists on the /Z option.
Vickers by Danfoss
KADG5V-5 / -7 / -8
Proportional directional with integral amplifier
7-pin plug (metal 934939 for EMC)A +24 V · B power 0 V · C signal 0 V · D command + · E command − · F monitor output (0.5 V per amp) · G PE±10 V differential, 47 kΩReduced
No electrical feedback of main-stage spool position on this valve. Spool-position measurements are unavailable; the monitor works from supply, current, the solenoid-current monitor output, vibration and acoustic emission.
Vickers by Danfoss
KDG5V-5 / -7 / -8 / -10
Proportional directional, no integral amplifier
ISO 4400 / DIN 43650 on the coilsCoil supply onlyDriven from an external amplifierReduced
The solenoid interface carries no command or feedback. Fit the monitor on the amplifier-to-valve run where the command exists, or accept supply, current, vibration and acoustic coverage only.

Not listed here? This is a sample of the interfaces we see most often, not the limit of what the monitor supports. The measurement hardware is the same regardless of connector — only the mating interface and the signal configuration change. Send us the data sheet and we will confirm fit and coverage before you commit.

Coverage by interface

What the monitor detects on each class of connector

Command + position feedback

Full coverage

6+PE, 11+PE, 12-pin and 7-pin interfaces carrying both a command and an actual-value signal.

  • Spool and sleeve wear
  • Silting
  • Erosion and internal leakage, with transmitters
  • Cavitation
  • Coil degradation
  • Valve electronics
  • Wiring and supply
Command, no position feedback

Reduced coverage

Interfaces carrying a command and a solenoid-current monitor but no spool position, such as the Vickers KADG5V.

  • Coil degradation
  • Cavitation
  • Wiring and supply
  • Valve electronics, in part
  • Hysteresis, threshold and null behaviour are unavailable
  • Silt lock cannot be measured directly
Coil supply only

Supply-side coverage

Form A, B and C solenoid connectors on valves with no on-board electronics.

  • Coil degradation
  • Cavitation
  • Wiring and supply
  • No command or position signal exists on this interface to measure
  • Better served by fitting the monitor on the amplifier-to-valve run